Sensing Input
Voltage: 95 – 132 VAC or 190 – 264 VAC
1 phase, jumper selectable
Frequency 50/60 Hz, selectable
Output
Voltage: Max. 90 VDC @ 207 VAC
Current: Continuous 4A
Intermittent 10A for sec
Resistance: Min. 15 ohm
Voltage Regulation
< ± 1.5 % ( with 4% engine governing)
Voltage Build-Up
Residual voltage at AVR terminal > 5 VAC
Thermal Drift
0.05% peer C change in AVR ambient.
External Volts Adjustment
±7% with 1k ohm 1 watt trimmer
Unit Power Dissipation
Max. 10 watt.
Under frequency Protection
Set point: 95% Hz
(UFRO)
Slope 170% down to 30 Hz
Soft Start Ramp Time
2 sec
Dimensions
135mm L * 100mm W * 49 mm H
Weight: 243g ± 2%